PROPERTY OF SOLIDSTATE CONTROLS, INC. 7/1998
As previously discussed, sealed batteries are those which, due to special construction, do not
normally vent gas into the atmosphere, and because they are sealed, require no routine water
additions. Because they do not gas, they are well suited for installation into an office area or
computer room environment where special ventilation would be difficult or impractical to
provide. These two advantages present cost savings which should be considered when
evaluating your battery requirements. Sealed batteries lend themselves well to cabinet
mountings, and as a result can be attractively packaged for installation in an office or computer
room along with the UPS system. One can also recognize sealed batteries by the use of
names such as Gel Cell, Absorbed Electrolyte, Starved Electrolyte, or Suspended Electrolyte.
Sealed batteries are maintenance free only in the sense they require no electrolyte
checks or water addition. It is important that the battery terminal connections be inspected and re-torqued
periodically to maintain a sound connection.
Life expectancy and manufacturer’s warranties vary from 1 year to 20 years with a corresponding
variation in price. As an average, a 10-year sealed battery on an open rack will be priced
approximately equal to the lead calcium 20 year wet battery.